Inspection
Inspection Details
Equipment ID
12648
12648
Inspection Date
8/22/2023
8/22/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
375
375
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
8ff66f80-eb67-4357-bd15-a705e80eabf1
8ff66f80-eb67-4357-bd15-a705e80eabf1
Location
CozySuites
4215 Lindell Blvd, St. Louis, MO
Phone: (469) 757-6150
Email: hello@cozysuites.co
4215 Lindell Blvd, St. Louis, MO
Phone: (469) 757-6150
Email: hello@cozysuites.co
Owner
Attn: CozySuites
CozySuites
4215 Lindell Blvd, St. Louis, MO 63108
Phone: (469) 757-6150
Email: hello@cozysuites.co
CozySuites
4215 Lindell Blvd, St. Louis, MO 63108
Phone: (469) 757-6150
Email: hello@cozysuites.co
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs to be programmed. | 12/17/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell shall work. | 12/17/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide maintenance control program. | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Provide on-site test records. | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace fire recall bezel, labeling worn off. | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Addjust care door restrictor for proper operation. | 3/3/2021 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | Adjust final limit switch for proper operation. | 3/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone. | 3/3/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperative. Re-inspection required | 8/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate | 8/29/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room door is damaged, difficult to close. Repair/replace as needed. | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. | 8/11/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The visual signal device did not light in the car when phase I was activated. Reinspection is required. | 8/11/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 7/29/2025 |