Inspection
Inspection Details
Equipment ID
12088
12088
Inspection Date
8/23/2023
8/23/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
fd99d1e2-490d-46ee-a072-ebea55621f7a
fd99d1e2-490d-46ee-a072-ebea55621f7a
Location
LaQuinta Inn
2214 TANEY ST, N KANSAS CITY, MO
Phone: (816) 221-1200
2214 TANEY ST, N KANSAS CITY, MO
Phone: (816) 221-1200
Owner
Attn: Jennifer Johnson
Relianse Kansas MO DBA LaQuinta Inn
2214 Taney St, N Kansas City, MO 64114
Phone: (816) 221-1200
Email: sue@premierhotelskc.com
Relianse Kansas MO DBA LaQuinta Inn
2214 Taney St, N Kansas City, MO 64114
Phone: (816) 221-1200
Email: sue@premierhotelskc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove sprinkler head from ceiling above controller, no heat detector or shunt trip present. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide an MCP in machine room to log maintenance, repairs, and inspections. | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide a 5 gallon pit jug in pit to collect leakage from jack packing. | 8/1/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | Main line disconnect has broken component inside, replace disconnect switch in machine room. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Handrail missing in car. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Handrail loose in car. | 8/1/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Stop switch on car operating panel worn, and not legible. Replace | 8/23/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Position indicator on COP not displaying floor numbers. | 8/1/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machine room door not self locking provide self looking door handle | 8/25/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach. room door lock defeatable | 10/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 10/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working not answered | 10/23/2023 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.14.2 Hydraulic Cylinders and Pressure Piping | Yes | Yes | leak down test failed dropped 2 inches in 15 mins futher testing required no shutoff valve | 10/23/2023 |