Inspection
Inspection Details
Equipment ID
15612
15612
Inspection Date
8/11/2023
8/11/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
300
300
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
28
28
External ID
ea26e9be-12e9-43ff-a167-0bb67d8bdf1f
ea26e9be-12e9-43ff-a167-0bb67d8bdf1f
Location
Melrose Hall
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 365-7641
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 365-7641
Owner
Attn: Stephany Guest
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
Billing
Attn: James Hoseth
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | phone does not operate | 1/15/2020 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not function | 1/21/2019 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Emergency auxillary power does not operate | 1/21/2019 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Post emergency evacuation of passengers procedure inside machine room. | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly. | |||
A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | Cylinder drain line needs to drain into pit container of no more than 5 gallon capacity. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter operating instructions on car operating panel. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter operating instructions next to hall fire keyswitch. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside machine room. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Test and log firefighter operation monthly | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Post emergency evacuation of passengers procedure in machine room | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside the machine room | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 1000.1b(3)(b) Metal Test Tag | Install metal test tag for periodic pressure relief test | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No MCP | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No maintenance records on site | |||
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | Identify inside of hoistway doors with a numeral | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 8/11/2023 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter instructions on car operating panel | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter instructions next to hall firefighter keyswitch | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 10/23/2024 | |
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | Identify inside of hoistway door with a numeral | |||
A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | Machine room door needs to be self-locking | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed in machine room | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Post In Case of Fire signage next to hall button fixture at each landing | |||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Auxiliary lowering unit does not operate | 10/23/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Battery lowering not working. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | "B" jamb tags missing due to vandalism. |