Inspection
Inspection Details
Equipment ID
20203
20203
Inspection Date
8/3/2023
8/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21F/25R
21F/25R
External ID
1630c4b7-6f29-4660-b490-993a8bca6d70
1630c4b7-6f29-4660-b490-993a8bca6d70
Location
Warehouse 7 Lofts
1227 Washington Ave, St. Louis, MO
Phone: (314) 621-8440
Alt Phone: (314) 323-7326
1227 Washington Ave, St. Louis, MO
Phone: (314) 621-8440
Alt Phone: (314) 323-7326
Owner
Attn: 1227 Washington LLC
1227 Washington LLC
1314 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: matt@mbdstl.com
1227 Washington LLC
1314 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: matt@mbdstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work with 24/7 support. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean the pit. | 10/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state elevator certificate. | 10/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be provided in the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to dial out | 5/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | The machine room needs to be cleaned. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | There is a laptop and an amplifier in the machine room providing music to the roof top patio that needs to be removed. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 8/1/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is standing water in the pit. The sump pump is not working. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump holes, with or without pumps, and well holes that are accessible, shall be covered flush with the pit floor. The covering shall consist of a noncombustible material | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | here is a laptop, audio wires, and an amplifier in the machine room providing music to the roof top patio that needs to be removed. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump holes, with or without pumps, and well holes that are accessible, shall be covered flush with the pit floor. The covering shall consist of a noncombustible material | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The Emergency Phone in the car fails to establish two-way communication. The phone dials an inactive number. |