A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone shall work.
|
2/7/2020
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
Yes
|
No
|
Bottom left hand cylinder needs to be looked at. 4" of rust on the bottom cylinder.
|
2/7/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
Yes
|
Yes
|
Water is leaking through drywall ceiling into the elevator controller in machine room causing an unsafe condition. Elevator has been Red-tagged and removed form service. Re-inspection required
|
10/20/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current operating certificate shall be on display in the machine room
|
1/27/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs to be repaired
|
1/27/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency lights in elevator cab do not work, needs repair. Re-inspection required
|
10/20/2023
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
Elevator cab ceiling is missing, leaving fluorescent light bulbs unprotected. Either re-install cab ceiling or guard bulbs against breakage.
|
1/27/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state operating certificate shall be displayed in the machine room
|
1/27/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs repaired.
|
1/27/2026
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
Elevator cab ceiling is missing leaving fluorescent light bulbs unprotected, Either re-install cab ceiling or guard bulbs against breakage.
|
1/27/2026
|