Inspection
Inspection Details
Equipment ID
14676
14676
Inspection Date
6/19/2023
6/19/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
480
480
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
13
13
External ID
b8292c57-fae1-40b9-b3bd-a7b4364b6d13
b8292c57-fae1-40b9-b3bd-a7b4364b6d13
Location
Bates County Memorial Hospital
615 W Nursery St, Butler, MO
Phone: (660) 679-4135
615 W Nursery St, Butler, MO
Phone: (660) 679-4135
Owner
Attn: Rob Clover
Bates County Memorial Hospital
615 W Nursery St, Butler, MO 64730
Phone: (660) 200-7068
Email: rclover@bcmhospital.com
Bates County Memorial Hospital
615 W Nursery St, Butler, MO 64730
Phone: (660) 200-7068
Email: rclover@bcmhospital.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | replace the emergency light battery, it is dead | 7/31/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | machine room lights were not working | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | the pit was full of water, maintain dry pit | 10/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | could not perform annual inspection because of water in pit and machine room lights not working | 11/24/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | the maintenance control program is missing the instructions for code checkout procedures | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device | Yes | Yes | elevator fail the set test, could not figure out where the oil was going. unit was red tagged | 11/18/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace burnt out cab ceiling lights, illumination inside the car does not meet the minimum requirements | 10/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Do not store non-Elevator related items in the machine room | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in the pit, provide means to prevent the accumulation of ground water in the pit | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Foam pad on tank lid is decomposing and dropping into the tank, clean or replace the oil | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Missing pickup roller on the bottom landing hoistway door | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Water in the pit, provide means to prevent the accumulation of ground water in the pit - repeat violation, now requires reinspection | 1/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Replace missing ceiling tiles in the machine room | 1/17/2026 |