Inspection
Inspection Details
Equipment ID
15779
15779
Inspection Date
7/25/2023
7/25/2023
Inspection Type
Alteration
Alteration
Inspector Name
Conde (Cache) Kinsella
Conde (Cache) Kinsella
Mechanic Name
Adam Schnurbusch
Adam Schnurbusch
Relief Valve Pressure
480
480
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
17
17
External ID
ba5da599-515f-4dec-b0a4-77cec76bf569
ba5da599-515f-4dec-b0a4-77cec76bf569
Location
Lambert St. Louis Int'l Airport
Lambert Field, St. Louis, MO
Phone: (314) 890-1331
Lambert Field, St. Louis, MO
Phone: (314) 890-1331
Owner
Attn: Construction & Maintenance Manager
St. Louis Lambert International Airport
10701 Lambert International Blvd, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
St. Louis Lambert International Airport
10701 Lambert International Blvd, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
Billing
Attn: Construction & Maintenance Manager
St. Louis Lambert International Airport
PO Box 10212, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
St. Louis Lambert International Airport
PO Box 10212, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Fire service call cancel button shall be labeled. | 11/8/2019 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Shall have proper access to car operating panel for maintenance and repairs. Current flooring does not allow panel to open. | 7/29/2020 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 4/16/2021 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 4/16/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/16/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 4/16/2021 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. | 9/9/2021 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | The wiring in the machine room shall be enclosed and electrical box covers shall be in place. | 7/27/2023 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Portions of the bottom of the car platform have rusted away and shall be repaired or replaced. Note: This is a plywood platform with a bottom liner of sheet metal. Large portions of the sheet metal are no longer there. This has a negative impact on the fire resistive integrity, and possibly the structural integrity of the platform. | 7/27/2023 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | A leak in the hydraulic system occurred near the completion of testing. The source of the leak shall be identified and corrected. | 7/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the leak in the hydraulic system, the following testing items still remain: The auxiliary power lowering operation shall be tested. | 7/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the leak in the hydraulic system, the following testing items still remain: The over-speed valve shall be tested with rated load. | 7/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the leak in the hydraulic system, the following testing items still remain: Fire service operation shall be tested. | 7/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the leak in the hydraulic system, the following testing items still remain: Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency Generator testing needs to be performed. Re-inspection required | 9/15/2023 |