Inspection
Inspection Details
Equipment ID
18482
18482
Inspection Date
8/29/2023
8/29/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Michael Collumbien
Michael Collumbien
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
217edd02-1f6e-4316-9644-dc1a39dc8a6d
217edd02-1f6e-4316-9644-dc1a39dc8a6d
Location
Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
Owner
Attn: Madison Himelright
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
Billing
Attn: Mike Jones
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | The elevator safety governor pull-through force is over the manufacturer’s required force. The governor or the governor rope shall be repaired/replaced and retested. The elevator is locked out of service. | 8/26/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The governor pull-through force shall be resolved before the testing of other components can be performed. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | Yes | 8.6.4.19.13 Broken-Suspension-Member and Residual-Strength Detection Means. The suspension belt monitoring system is disabled/malfunctioning. With no monitoring means, the suspension belts were visual inspected with a significant amount of rouge present. This unit shall be removed from service until the suspension belts have been replaced and a repaired/replaced suspension belt monitoring system is in place. | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.19.13 Broken Suspension Member and Residual Strength Detection Means | Yes | Yes | The suspension belt monitoring system has been disabled allowing the elevator to remain in service. This system is designed and required to place the elevator out of service when detection shows immediate replacement of the suspension belts. Suspension belt detection monitoring shall be re-enabled to operate as required. | 6/7/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power testing and fireman’s emergency operation shall be performed before the inspection is completed. | 6/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power testing and fireman’s emergency operation shall be performed before the inspection is completed. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Elevator machine room air conditioning does not work, needs repaired | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test elevator for phase I & II fire service. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean dirt from elevator pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor does not work. There is too much clearance between the collapsible vane and hoistway brackets. Re-inspection required |