Inspection
Inspection Details
Equipment ID
4106
4106
Inspection Date
8/2/2023
8/2/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
aa39a687-d35a-4ee1-b750-eccc78bf5a5e
aa39a687-d35a-4ee1-b750-eccc78bf5a5e
Location
Renaissance Hotel (9th & St. Charles Garage)
419 N 9Tth St, St. Louis, MO
Phone: (314) 621-4221
419 N 9Tth St, St. Louis, MO
Phone: (314) 621-4221
Owner
Attn: MO Development Finance Board
MO Development Finance Board
PO Box 567, Jefferson City, MO 65102
Phone: (314) 241-7777 Ext: 112
MO Development Finance Board
PO Box 567, Jefferson City, MO 65102
Phone: (314) 241-7777 Ext: 112
Billing
Attn: Kenny Darragh
St. Louis Parking Company
1617 S 3rd, St. Louis, MO 63104
Phone: (314) 456-5664
Email: kennyd@stlouisparking.com
St. Louis Parking Company
1617 S 3rd, St. Louis, MO 63104
Phone: (314) 456-5664
Email: kennyd@stlouisparking.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working due to bad phone line. Reinspect. | 8/23/2018 |
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 1001.2(c)(1) | No | No | Replace broken car top stop switch. | 11/4/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Remove dead pigeons and feces from elevator machine room. | 11/4/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher outdated. Update fire extinguisher | 12/21/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/10/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 11/10/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 11/10/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The 5 year test is complete with the following exceptions: 1. Rated speed full load safety test (125% load test and full load rated speed car buffer tests have been successfully completed), 2. Fire service operation, 3. Rated speed counterweight buffer test with an empty car. | 11/10/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location, message, full address and unit number. | 9/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work properly. It is too dim at COP and is mounted incorrectly. | 9/28/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP, including PM records and monthly fire service test log are not being properly documented. | 9/23/2025 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door shall be self-closing and self-locking. | 9/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | G-level hall station is damaged (pushed into wall). | 9/23/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 9/23/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall work. | 9/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work properly. It is too dim at COP and is mounted incorrectly. | 8/26/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication/phone in car is not working. | 10/3/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | The MCP, including PM records and monthly fire service test log are not being properly documented. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two-way communication are inoperable and shall be repaired or replaced. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide means for pit light to correctly operate. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Yes | No | Emergency lighting shall work properly. It does not work and is incorrectly mounted. |