Inspection
Inspection Details
Equipment ID
13748
13748
Inspection Date
8/15/2023
8/15/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
15d82d93-125c-4188-b445-11ac48673fb0
15d82d93-125c-4188-b445-11ac48673fb0
Location
Vangard Loft Apartments
1110 Washington Ave, St. Louis, MO
Phone: (314) 484-1543
1110 Washington Ave, St. Louis, MO
Phone: (314) 484-1543
Owner
Attn: Vangard Acquisitions, LLC
Vangard Acquisitions, LLC
1110 Washington Ave, St. Louis, MO 63101
Phone: (314) 588-9992
Email: jmccombs@maxusprop.com
Vangard Acquisitions, LLC
1110 Washington Ave, St. Louis, MO 63101
Phone: (314) 588-9992
Email: jmccombs@maxusprop.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair machine room lighting | 6/10/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lighting. | 6/10/2019 |
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | No | No | Counterweight slide guides are wore out and not usable. counterweights getting ready to come off guide rails. Elevator removed from service. Reinspect before use. | 6/10/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC type fire extinguisher shall be provided in the elevator machine room. | 6/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 8/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 9/12/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is an excessive amount of water in the pit that shall be removed. The pit shall be kept clean and dry. | 8/24/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | In the stairway leading up to the roof where the machine room is located there is a step that has a significant crack from end to end. Once on the roof there are also other steps that are damaged. These steps shall be repaired to provide safe and convenient access to the machine room. | 8/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate displayed in the machine room. | 10/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 8/10/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 8/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | A permanent and unobstructed means of access to elevator machine rooms and overhead machinery spaces shall be provided. The top of the stairway leading to the roof isn't lighted, and should be. | 8/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The machine room temperature shall be kept within the manufacturers recommended range. The air conditioner is not working. | 8/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | The key switches required by 2.27.3 for all elevators in a building shall be operable by the same key. The two elevators in the building are using different fire service keys. They should be keyed the same. | 9/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way emergency communications device is not functioning and needs repair. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service jewel in car not illuminated on phase I or phase II operation. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit shall be removed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |