ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
post emergency evacuation of passengers procedure form inside machine room.
|
8/2/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
provide firefighter key in machine room or on site.
|
9/2/2020
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
test firefighter service monthly and provide written documentation in machine room or on site.
|
8/2/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
car door restrictor does not function.
|
9/2/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Test and log firefighter operation monthly
|
11/5/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Provide sump pump. Install sump pump and drain line. Oil alarm per local plumbing code. Drain line shall not directly connect with sewer.
|
11/5/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
|
|
Post In Case of Fire signage next to hall button fixture at each landing
|
9/27/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
CAR DOOR RESTRICTOR DID NOT WORK
|
7/17/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.19 - Car Ride
|
8.11.2.1.1(s)
|
|
|
CAR HAS A BAD SHAKE AS IT TRAVELS UP & DOWN THE HOISTWAY
|
11/4/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
HOISTWAY ACCESS DID NOT WORK IN THE UP DIRECTION
|
11/4/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working bad phone board
|
11/4/2025
|