Inspection
Inspection Details
Equipment ID
20408
20408
Inspection Date
8/30/2023
8/30/2023
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Thomas Nortley
Thomas Nortley
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
700a7161-cfee-4c56-97fe-2c7c9071aaee
700a7161-cfee-4c56-97fe-2c7c9071aaee
Location
KSDK-TV-5
6871 Heege Rd, Affton, MO
Phone: (314) 444-5187
Email: dspina@ksdk.com
6871 Heege Rd, Affton, MO
Phone: (314) 444-5187
Email: dspina@ksdk.com
Owner
Attn: Daniel Spina
KSDK-TV 5
1000 Market St, St. Louis, MO 63101
Phone: (314) 444-5187
Email: dspina@ksdk.com
KSDK-TV 5
1000 Market St, St. Louis, MO 63101
Phone: (314) 444-5187
Email: dspina@ksdk.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)12 | A mechanical inspection was performed with the controller hard wired on 11/9/2018. Radio control was not functioning on 11/9/2018. Radio control operation shall be tested once repaired. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Radio car control shall be operational. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | x | Due to radio control not being operational, the following items are not functioning: Gate switch, car push buttons, and car stop switch. This unit has been Red Tagged and placed out of service. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Rope data tags shall be provided | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Category 1 and category 5 testing tags shall be provided. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | A capacity tag shall be provided in the car. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | x | Two-way communication shall be operational. | |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | Car safeties shall be operational. - Unit Red Tagged. | |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | x | Bottom directional and bottom final limit switches shall be operational. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevators Placed out of Service | x | x | Unit has be removed from service. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevators Placed out of Service | x | x | Inspection to de-commission radio tower elevator. Suspension ropes are removed. Electric feeder has been removed. Car & counterweights are on buffers. |