Inspection
Inspection Details
Equipment ID
5866
5866
Inspection Date
8/22/2023
8/22/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
440
440
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
2003f647-eb8c-440c-91b2-46b116bc01e6
2003f647-eb8c-440c-91b2-46b116bc01e6
Location
9326 Olive Building
9326 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 932-4242
9326 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 932-4242
Owner
Attn: Thomas Boggs
Boggs, Avellino, Lach & Boggs
9326 Olive Blvd, St. Louis, MO 63132
Phone: (314) 274-2203
Boggs, Avellino, Lach & Boggs
9326 Olive Blvd, St. Louis, MO 63132
Phone: (314) 274-2203
Billing
Attn: Melissa Stewart
Boggs, Avellino, Lach & Boggs
9326 Olive Blvd, St. Louis, MO 63132
Phone: (314) 274-2203
Email: mstewart@balblawyers.com
Boggs, Avellino, Lach & Boggs
9326 Olive Blvd, St. Louis, MO 63132
Phone: (314) 274-2203
Email: mstewart@balblawyers.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Can not hear the emergency phone operator, fix the volume of the emergency phone so as to hear the operator. | 11/27/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The machine room door shall be self-locking. | 1/29/2020 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 1200.6 | No | No | A code data plate is required. The code data plate shall read: A17.1-1996 | 1/29/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Verify that the heat detector located in the machine room and at the top of the hoistway do not affect the operation of the elevator. | 11/27/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Cannot hear the emergency phone operator, fix the volume of the emergency phone so as to hear the operator. | 1/27/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/2/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - Emergency lowering device(ERU) shall be operational. | 10/2/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | The machine room fire extinguisher shall have a current test tag. | 10/2/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/31/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 8/31/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. Note: The log isn't being filled out monthly. | 9/21/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor. | 9/21/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/1/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire Service testing shall be performed and documented monthly. | 11/1/2025 |