Inspection
Inspection Details
Equipment ID
18704
18704
Inspection Date
7/13/2023
7/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
510
510
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24F/21R
24F/21R
External ID
9015da95-b735-4d55-a32b-f2ec62143283
9015da95-b735-4d55-a32b-f2ec62143283
Location
CBC High School
1850 De La Salle Dr, St. Louis, MO
Phone: (314) 985-6100
1850 De La Salle Dr, St. Louis, MO
Phone: (314) 985-6100
Owner
Attn: CBC High School
CBC High School
1850 De La Salle Dr, St. Louis, MO 63141
Phone: (314) 985-6076
Email: crouchf@cbchs.org
CBC High School
1850 De La Salle Dr, St. Louis, MO 63141
Phone: (314) 985-6076
Email: crouchf@cbchs.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/14/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 7/14/2021 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall be cleaned. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 7/14/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | The machine room shall be kept clean. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. Clean the pit. | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | The car top shall be kept clean. Clean the car top. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work without breaking up and disconnecting. | 4/29/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work. | 9/24/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |