Inspection
Inspection Details
Equipment ID
4635
4635
Inspection Date
9/13/2023
9/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Brian Foster Sr.
Brian Foster Sr.
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
0240315e-fa7c-48f1-b4f5-470cc04cb4bd
0240315e-fa7c-48f1-b4f5-470cc04cb4bd
Location
Hillyard Industries
402 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 233-1321
402 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 233-1321
Owner
Attn: Hillyard Industries
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Billing
Attn: Hillyard Industries
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Need to post "C-1 Loading No Passengers" sign inside elevator. | 1/16/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Need to post sign inside the elevator "C-1 LOADING NO PASSENGERS" | 1/16/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 1/16/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Post emergency evacuation of passengers form inside machine room | 1/16/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Front car gate photo eye does not reopen door | 9/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Replace broken hoistway door guide shoe at level 1R. | 9/22/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris from pit. | 1/16/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Post "C-1 LOADING NO PASSENGERS" sign inside elevator. | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Front car gate photo eye does not reopen gate. | 9/13/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | No lighting provided in machine room. Need to repair lighting. | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris from elevator pit | 1/16/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove debris from machine room floor. | 1/16/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | All elevators in the same building shall have firefighter keyswitches operated by the same key. | 1/16/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly. | 1/16/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove fire hazard debris from pit. | 1/16/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Fire hat blinks when firefighter keyswitch is turned to on position for fire recall. The fire hat should be on solid during this recall. | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan in machine room. | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records in the machine room | 1/16/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 1/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove wood pallet debris from elevator pit. | 1/16/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit, remove. | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | CLEAN PIT |