Inspection
Inspection Details
Equipment ID
20650
20650
Inspection Date
9/13/2023
9/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
ae817650-f82d-4419-bb37-29e33eee482c
ae817650-f82d-4419-bb37-29e33eee482c
Location
Stifel Theatre
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
Owner
Attn: Adrian Silverstein
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Billing
Attn: Scottrade Center
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Replace or have serviced | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car safeties need to be tested after safety drum rope is replaced. Re-inspection required | 9/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction. Re-inspection required | 9/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch, located next door in the security office. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Post Phase I instructions near the f/f switch in the lobby. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Observed numerous ledges exceeding 4”code requirement, repair as needed. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct car speed on the cross head data plate. | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Shorten suspension cables to get a minimum of 6" counterweight runby | 4/10/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 4/10/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 4/10/2026 |