Inspection
Inspection Details
Equipment ID
13130
13130
Inspection Date
9/14/2023
9/14/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Matthew Whaley
Matthew Whaley
Relief Valve Pressure
420
420
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
19
19
External ID
0ae9be58-6a1e-4931-b286-90fb169b2806
0ae9be58-6a1e-4931-b286-90fb169b2806
Location
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO
Phone: (573) 893-3700
4712 Country Club Dr, Jefferson City, MO
Phone: (573) 893-3700
Owner
Attn: Missouri Hospital Association
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO 65109
Phone: (000) 000-0000
Email: cbranum@mail.mhanet.com
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO 65109
Phone: (000) 000-0000
Email: cbranum@mail.mhanet.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | No non-elevator related equipment can be stored in elevator equipment room | 11/11/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non elevator related items in machine room | 6/6/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. The car currently is not equipped with a telephone line, so the phone and the phone monitor could not be tested. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 5/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | The data on the door operator tag shall be filled out. | 5/22/2024 |
| A17.1-2016 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Yes | No | The car-top emergency exit shall be secured to prevent it from falling down the hoistway. If a chain is used, it shall be not more than 12" in length and have a factor of safety of not less than 5. | 5/22/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | 2.1.6.1 - The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation. | 5/22/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The in car keyed stop switch shall not be made ineffective on phase one fire service. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. | 6/12/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. | 6/12/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | MUST FILL ALL HOLES IN HOISTWAY |