Inspection
Inspection Details
Equipment ID
13468
13468
Inspection Date
10/15/2018
10/15/2018
Inspection Type
Major Alteration
Major Alteration
Inspector Name
David Hardin
David Hardin
Mechanic Name
Vincent Langendoerfer
Vincent Langendoerfer
Relief Valve Pressure
Slide
117
117
Governor Rope Pull
325/930
325/930
Door Closing Force
25
25
External ID
e4bce0b3-9bf1-4032-82b1-032d9078790f
e4bce0b3-9bf1-4032-82b1-032d9078790f
Location
Hanley Cooperation Tower
101 S HANLEY RD, CLAYTON, MO
101 S HANLEY RD, CLAYTON, MO
Owner
Hanley Corporate Tower
101 S HANLEY RD STE 1130, CLAYTON, MO 63105-3491
101 S HANLEY RD STE 1130, CLAYTON, MO 63105-3491
Billing
Attn: Hanley Corporate Tower
101 S HANLEY RD STE 1130, CLAYTON, MO 63105-3491
101 S HANLEY RD STE 1130, CLAYTON, MO 63105-3491
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Testing procedures not in machine room. | 10/16/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site posted on controller | 2/12/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Rope shackle is rubbing on counterweight frame causing c/w frame to start thinning, this is the same violation found on last years inspection, need a permenant fix to the problem | 2/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Rope gripper pads need to be replaced. | 9/17/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Need to include testing procedures in MCP on or before January 1,2022 | 9/17/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 10/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Provide testing procedures in the maintenance control program | 10/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 7/21/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | complete annul test within 14 days unintended motion, alternate fire floor | 7/21/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Make repairs & reschedule for a complete 5 yr full load test within 30 days | 4/11/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | Yes | Adjust counterweight governor for proper setting | 5/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Repair phone in car emergency light and bell in the car | 5/6/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Complete 5 year test | 5/6/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test emergency generator | 11/4/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency generator | 2/8/2025 |