Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Michael Loftin
Michael Loftin
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
63e81c94-a3b2-4c4c-8398-284d69a4417c
63e81c94-a3b2-4c4c-8398-284d69a4417c
Location
Ferrell-Duncan : The Bone & Joint Center
3555 S National Ave, Springfield, MO
Phone: (417) 875-3988
Email: steve.graham@coxhealth.com
3555 S National Ave, Springfield, MO
Phone: (417) 875-3988
Email: steve.graham@coxhealth.com
Owner
Attn: Steve Graham - Maintenance
Ferrell Duncan Building
1001 E Primrose, Springfield, MO 65807
Phone: (417) 875-3261
Fax: (417) 875-3297
Email: steve.graham@coxhealth.com
Ferrell Duncan Building
1001 E Primrose, Springfield, MO 65807
Phone: (417) 875-3261
Fax: (417) 875-3297
Email: steve.graham@coxhealth.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | needs current certificate posted | 9/25/2024 | ||
conversion | conversion | n/a | Install metal tags for annual & 5 yr safety test to governor | 9/25/2024 | ||
A17.1-1996 : Elevators | 2.16 -Overhead Beam and Fastenings | 105.3 | Isolation pads under machine need replaced | 9/25/2024 | ||
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | suspension ropes (red rust or rouge) need attention--lubricated | 9/24/2019 | |
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | vacume up red dust in machine room NOTE caution smoke detectors in the machine room | 9/25/2024 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | current certificate needs to be posted in machine room | 9/25/2024 | ||
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete | 6/30/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP / Fire test log on-site | 9/25/2024 | ||
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 3.23: Ropes replaced, no rope data tag . | 5/27/2022 | |
A17.1-1996 : Elevators | 2.16 -Overhead Beam and Fastenings | 105.3 | Isolation pads under machine need replaced | 6/29/2021 | ||
A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | x | Install metal tags for annual and 5 yr safety test to governor | 6/29/2021 | |
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete | 6/29/2021 | |
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 3.23: Ropes replaced, no rope data tag | 5/27/2022 | |
A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | 206.5 : Governor rope shall be shortened for proper alignment of tail sheave. REINSPECTION >6/27/22 | 12/28/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | REPAIR 4TH FLOOR DOOR GUIDES AND UPTHRUST BEARINGS | 9/25/2024 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate in machine room | 9/25/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide current MCP in machine room | 9/25/2024 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | provide operational telephone in cab | 11/4/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | provide onsite MCP |