Inspection
Inspection Details
Equipment ID
14082
14082
Inspection Date
8/28/2023
8/28/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
0ef79560-4ffb-400e-83f9-dc5060a1da38
0ef79560-4ffb-400e-83f9-dc5060a1da38
Location
Fire House #2
11804 Big Bend Rd, Kirkwood, MO
Phone: (314) 822-5883
11804 Big Bend Rd, Kirkwood, MO
Phone: (314) 822-5883
Owner
Attn: Kirkwood, City of
Kirkwood, City of
139 S Kirkwood Rd, Kirkwood, MO 63122
Phone: (000) 000-0000
Kirkwood, City of
139 S Kirkwood Rd, Kirkwood, MO 63122
Phone: (000) 000-0000
Billing
Attn: Kirkwood, City of
Kirkwood, City of
212 S Taylor Ave, Kirkwood, MO 63122
Phone: (814) 984-5947
Email: Wallsta@kirkwoodmo.org
Kirkwood, City of
212 S Taylor Ave, Kirkwood, MO 63122
Phone: (814) 984-5947
Email: Wallsta@kirkwoodmo.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/13/2019 |
| A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 1002.2e | Yes | No | Car shall stop in the down direction while on car top inspection prior to striking the buffer. When the car strikes the buffer, it activates the low pressure switch, rendering the car inoperable. | 11/13/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 11/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 11/22/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The annual inspection was not completed. The following items shall be tested: Relief pressure, pressure switch, low oil timer. | 8/4/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 full load test shall be performed on the overspeed valve in 2022. | 9/2/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP, including PM records and monthly fire service test log are not being properly documented. | 2/14/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 2/14/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. Take corrective action as needed. | 8/28/2023 |