Inspection
Inspection Details
Equipment ID
10038
10038
Inspection Date
9/1/2023
9/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
7b506f39-459d-4892-a5a9-bf42c5ab518b
7b506f39-459d-4892-a5a9-bf42c5ab518b
Location
University Club Tower
1034 S Brentwood Blvd # PH1A, Richmond Heights, MO
Phone: (314) 727-6664
Email: aaltman@stlcre.com
1034 S Brentwood Blvd # PH1A, Richmond Heights, MO
Phone: (314) 727-6664
Email: aaltman@stlcre.com
Owner
Attn: CF Clayton Office 2 LP
CF Clayton Office 2 LP
1034 S Brentwood Blvd, Richmond Heights, MO 63117
Phone: (314) 863-3700
Email: choltzman@stlcre.com
CF Clayton Office 2 LP
1034 S Brentwood Blvd, Richmond Heights, MO 63117
Phone: (314) 863-3700
Email: choltzman@stlcre.com
Billing
Attn: CF Clayton Office 2 LP
CF Clayton Office 2 LP
1034 S Brentwood Blvd, Richmond Heights, MO 63117
Phone: (314) 863-3700
Email: ap@stlcre.com
CF Clayton Office 2 LP
1034 S Brentwood Blvd, Richmond Heights, MO 63117
Phone: (314) 863-3700
Email: ap@stlcre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Make car door restrictor operational. | 6/6/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 8/28/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency power shall be tested. | 9/30/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to simulate the fire alarm initiating devices for phase 1 recall. | 9/30/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate in the elevator machine room. | 8/28/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance documents (MCP). | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 8/28/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 8/28/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing shall be completed. The following testing items remain: Counterweight buffer shall be tested at contract speed, 125% brake test, car safeties shall be set at contract speed with full load, and car buffer shall be tested with full load at contract speed. | 9/13/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be tested and shall operate with and without main power. | 9/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested to complete the annual inspection. | 9/19/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/28/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested as required. | 8/12/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The standby power selector switch and light shall be removed or marked "for future use" - the building is not equipped with emergency power for the elevators. | 8/28/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device is not functioning and needs repair. | 8/28/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/28/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 8/28/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A maintenance control program shall be provided in machine room. | 8/28/2026 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Lighting in machine room shall be not less than 10fc at floor level. Recommend adding light fixture over controller as personnel are having a hard time seeing equipment. | 8/28/2026 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | Counterweight runby does not meet Code Minimum of 6". | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire Service Phase 1 and 2 shall be tested to complete CAT5. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Lighting in machine room shall be not less than 10fc at floor level. Recommend adding light fixture over controller as personnel are having a hard time seeing equipment. | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Cartop shall be kept free of excess debris/dirt/lint. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP, including PM records, not being retained properly. MCP/Records shall be kept in the Machine Room for 5 years. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | MCP - Fire Service must be tested and properly documented monthly on an on-site Log Sheet | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | Hoistway doors shall be self-closing | |
| A17.1-1996 : Elevators | 5.6 - Governor-rope tension devices | 1001.2(e)(7) | No | No | Governor Tail Sheave only has about 1" of travel remaining. |