A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
AMaintenanceControlProgramforeachunit(see 8.6.1.1.1) shall be provided by the person(s) and/or firm maintaining the equipment and shall be viewable on- site by elevator personnel at all times from time of acceptance inspection and test or from the time of equip- ment installation or alteration
|
8/1/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.27 - Crosshead data plate
|
8.11.2.1.3(k)
|
No
|
No
|
Need crosshead data plate
|
8/1/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
No
|
No
|
Safety Retainers missing from bottom of Hoistway doors.The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail,
|
8/1/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6
|
8/1/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
No
|
No
|
2.11.11.8 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
8/1/2023
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
Yes
|
No
|
Hoist Ropes showing excessive rouge have stretched reducing diameter beyond maximum allowable amount. Replace hoist ropes.
|
9/21/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
Provide Crosshead Data Tag
|
8/1/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
No
|
No
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
1/17/2024
|
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
8.11.2.1.3(k)
|
No
|
No
|
Provide Crosshead Data Plate compliant with section 2.16.3
|
1/17/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The Emergency Phone in the car fails to establish two-way communication.
|
10/8/2025
|