Inspection
Inspection Details
Equipment ID
15718
15718
Inspection Date
8/22/2023
8/22/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
NA
NA
Slide
TBD
TBD
Governor Rope Pull
60/780
60/780
Door Closing Force
28
28
External ID
46dc8428-cd16-4f5b-a1f3-77e1ab7cef39
46dc8428-cd16-4f5b-a1f3-77e1ab7cef39
Location
Peper Lofts
701 N 1st St, St. Louis, MO
Phone: (314) 260-9266
Email: bwright@advantesgrp.com
701 N 1st St, St. Louis, MO
Phone: (314) 260-9266
Email: bwright@advantesgrp.com
Owner
Attn: Jasmina Hozbo
Peper Lofts
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 260-9266
Alt Phone: (314) 574-9321
Email: accountspayable@advantesgrp.com
Peper Lofts
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 260-9266
Alt Phone: (314) 574-9321
Email: accountspayable@advantesgrp.com
Billing
Attn: Alan Luffy
Peper Lofts
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 474-0528
Alt Phone: (314) 788-3220
Email: accountspayable@advantesgrp.com
Peper Lofts
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 474-0528
Alt Phone: (314) 788-3220
Email: accountspayable@advantesgrp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | No | No | Car door restrictor does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | High voltage (110V) wiring on car top shall be enclosed in conduit. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Hoistway duct covers shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Suspension rope data tags shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump pump cover shall be installed flush with the pit floor. | 1/4/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Weight related testing of safeties, buffers, and machine brakes shall be completed. | 11/8/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door restrictor shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be posted in the machine room in a non-combustible frame. | 10/27/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | A counterweight guard shall be installed. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency light shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall operate on auxiliary power. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | Yes | Fire service phase 1 instructions shall be posted at the hall key switch, and fire service phase 2 instructions shall be posted in the car. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service phase 1 & phase 2 key switches shall be legible. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The 3rd landing car call shall be operational on fire service phase 2. | 9/22/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking and self-closing. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The machine room fire extinguisher shall be tagged to verify that the extinguisher is current. | 10/27/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Traveling cables in the machine room shall be enclosed in wireway. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A code data plate is required. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Provide code compliant counterweight runby. | 8/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete. Full load buffer testing, setting the safeties, and no load counterweight buffer test still need to be completed. | 8/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be provided in the machine room. |