Inspection
Inspection Details
Equipment ID
26505
26505
Inspection Date
9/5/2023
9/5/2023
Inspection Type
New Installation
New Installation
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
460
460
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
54eb808a-372b-4081-92fc-2380af6f6c83
54eb808a-372b-4081-92fc-2380af6f6c83
Location
Woodstone Self-Storage
1610 Woodstone Dr, St. Charles, MO
Phone: (314) 960-6006
Email: garen@garenmiller.com
1610 Woodstone Dr, St. Charles, MO
Phone: (314) 960-6006
Email: garen@garenmiller.com
Owner
Attn: Nitneil Woodstone Storage LLC
Nitneil Woodstone Storage LLC
1447 Peachtree St, Ste 470, Atlanta, GA 30309
Phone: (000) 000-0000
Nitneil Woodstone Storage LLC
1447 Peachtree St, Ste 470, Atlanta, GA 30309
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 11/3/2023 | |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | The machine room temperature shall be kept within the manufacturers recommended range. | 11/3/2023 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Penetrations on the inside of the hoistway wall where the sprinkler pipes enter shall be patched with approved material. | 11/3/2023 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | The penetration in the wall above the machine room door shall be patched with approved material. | 11/3/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | x | All wiring in the hoistway shall be enclosed | 11/3/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | The sump pump shall have the capacity to remove a minimum of 3,000 GPH per elevator | 11/3/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | The lighting in the pit shall provide an illumination of not less than 10 fc at the pit floor. | 11/3/2023 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | The machine room door wasn't equipped with a permanent label indicating the fire rating. The contractor drilled the door and installed a tag. The door may not have the required fire rating | 11/3/2023 | |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | x | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key | 11/3/2023 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | x | x | 2.27.3.2.1 - When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of A17.1 2016 and shall be located in the pit per NFPA 72 21.3.7(2). Also, Smoke detectors shall not be installed in elevator pits to initiate elevator recall unless the smoke detector is listed for the environment per NFPA 72 2.3.8. Note(1): Exception - A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoist-way (the elevator pit), provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. Note (2): The sprinklers in the pit are required by NFPA13 8.15.5 and permitted by A17.1 2016 2.8.3.3 | 11/3/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | The elevator manufacturer requires the overhead hoisting beam to be labeled for capacity. | 11/3/2023 |