Inspection
Inspection Details
Equipment ID
6832
6832
Inspection Date
9/21/2023
9/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
91c6ba4d-c221-4d97-969a-2e2143996a47
91c6ba4d-c221-4d97-969a-2e2143996a47
Location
The Ritz-Carlton
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
Owner
Attn: Ritz Carlton Hotel
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Alarm bell on left hand Car Operating Panel when button or Stop switch is pressed | 11/28/2022 | ||
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | One of two emergency lamps is not working (right-hand COP). | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting is less than the required 19fc at controller. | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room outlets are not GFCI protected. | 6/26/2024 | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | x | Hoist Rope Tail retaining clips shall be properly spaced. | 6/26/2024 | |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Cartop needs 4" toe kick around perimeter under handrails. | 6/26/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 | x | Pit stop switch to be reachable from access door. | 6/26/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit lighting is less than the required 10fc. | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | x | Mainline disconnect failed to trip when heat detector is activated. | 6/26/2024 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | x | x | Main floor smoke sent elevator to main floor. | 6/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test fire service phase 1 & 2. | 6/26/2024 | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | One of two emergency lamps is not working (right-hand COP). | 3/21/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting is less than the required 19fc at controller. | 3/21/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room outlets are not GFCI protected. | 3/21/2025 | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | x | Hoist Rope Tail retaining clips shall be properly spaced. | 3/21/2025 | |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Cartop needs 4" toe kick around perimeter under handrails. | 3/21/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit lighting is less than the required 10fc. | 3/21/2025 |