Inspection
Inspection Details
Equipment ID
24536
24536
Inspection Date
9/12/2023
9/12/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
df8fd8aa-1303-4edd-945c-46a9e223247e
df8fd8aa-1303-4edd-945c-46a9e223247e
Location
Steelcote Lofts
801 Edwin St, St. Louis, MO
Phone: (314) 721-8427
801 Edwin St, St. Louis, MO
Phone: (314) 721-8427
Owner
Attn: Steelcote Lofts Condo Assoc
Steelcote Lofts Condo Assoc
801 Edwin St, St. Louis, MO 63103
Phone: (314) 924-6045
Email: steelcote@2bresidential.com
Steelcote Lofts Condo Assoc
801 Edwin St, St. Louis, MO 63103
Phone: (314) 924-6045
Email: steelcote@2bresidential.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | Provide 19 ft at the floor level in front of control on top floor. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | Yes | No | Bevel all ledges at 4" or greater. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | Seal all hoistway penetration. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Glass in rear hoistway wall shall be laminated ANSI Z97 rated and etched. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | Yes | No | Sump pump shall be 3000 GPM or larger and not tied directly to the sewer. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Install ABC fire extinguisher on car top. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | Yes | No | Hoistway signage shall be permanent and read ELEVATOR HOISTWAY. | 7/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No current maintenance records on site. | 9/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current operating certificate on display. | 9/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car door restrictor does not work. | 6/24/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car door restrictor does not work. Repair or replace 8.6.4.13.1 (l) | 9/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Need to clean pit to remove debris, water and /or oil and address sources | 2/28/2024 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Car door restrictor does not work, needs repaired. Re-inspection required | 7/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Phone in elevator is not working. Red-tagged, Re-inspection required | 7/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | There is no alarm bell in elevator. Red-tagged, re-inspection required | 7/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor is not working, needs repaired. Re-inspection required | 7/21/2025 |