Inspection
Inspection Details
Equipment ID
2598
2598
Inspection Date
9/11/2023
9/11/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Mark Hefner
Mark Hefner
Relief Valve Pressure
490
490
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
c115da96-7d8c-450b-969d-86a0447ca660
c115da96-7d8c-450b-969d-86a0447ca660
Location
Track & Soccer Complex
Providence & Stadium, Columbia, MO
Phone: (573) 882-6463
Providence & Stadium, Columbia, MO
Phone: (573) 882-6463
Owner
Attn: Facility Operations
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Insufficient machine room lighting | 11/13/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Telephone not dialing to a monitored location | 5/13/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | No emergency light/alarm | 5/13/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State operating certificate in machine room | 5/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire service hall key switch bezzel faded and unreadable | 5/27/2020 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Provide a 110V AC GFI outlet in machine room | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing fire service Phase 1 instructions at main landing | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing fire service Phase 2 instructions in car | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | G) 8.6.1.6.7 Replace missing "Do not use elevator in case of fire" Signage on 2nd landing. | 9/26/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Reinstall cover, rear wall of pit, to cover water fountain plumbing. | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | Need to install code data plate on controller. | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to add Fire service Phase I instructions at main landing | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Phase II instructions inside elevator cab | 12/7/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Need to install cover over exposed water pipes in back wall of hoistway. Repair leaks in water pipes that belong to the drinking fountains outside hoistway in back | 12/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has water in it, pits should be kept clean & dry | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to install code data plate on controller. | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Need Fire service Phase I instructions on main landing | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Replace missing Phase I instructions inside elevator cab | 7/30/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Install cover over exposed water pipes in back wall of hoistway. Repair leaks in water pipes that belong to the drinking fountains outside hoistway in back. | 7/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has water in it, pit should be kept clean & dry | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair programming of this phone for proper operation and passenger safety. Re-inspection required | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace Fire service Phase I instructions at Main Landing | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Phase I instructions inside the elevator cab | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Seal all holes in machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Relamp machine room lights as needed. |