Inspection
Inspection Details
Equipment ID
23860
23860
Inspection Date
9/26/2023
9/26/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
Na
Na
Slide
11
11
Governor Rope Pull
200/500
200/500
Door Closing Force
Na
Na
External ID
ac2e8039-437f-4c22-b5fc-d7ba96b7614d
ac2e8039-437f-4c22-b5fc-d7ba96b7614d
Location
U Haul of St Louis
4230 Gravois Ave, St. Louis, MO
Phone: (000) 000-0000
4230 Gravois Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: U-Haul- International
U-Haul- International
PO Box 21502, Phoenix, AZ 85036
Phone: (314) 355-7920
U-Haul- International
PO Box 21502, Phoenix, AZ 85036
Phone: (314) 355-7920
Billing
Attn: U-Haul Company of St. Louis
UHaul Co of Missouri NE
418 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 766-4009
Email: erica_norman@uhaul.com
UHaul Co of Missouri NE
418 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 766-4009
Email: erica_norman@uhaul.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | Yes | No | 1. All materials exposed to the car interior and the hoistway shall be metal, glass, or shall conform to 2.14.2.1.1 through 2.14.2.1.6. Protective wrapping of cab interior has not been removed. Ref: 2.14.2.1 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | 2. A data plate conforming to 2.16.3.3 shall be attached to the power door operator or to the car crosshead and shall contain the following information: minimum door closing time in seconds for the doors to travel the Code zone distance. Data plate blank. Ref: 2.13.4.2.4 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | 3. Hoistway enclosures shall have flush surfaces on the hoistway side. All nails, screws and other protrusions shall be removed, so as to be flush with wall, throughout the hoistway. Ref: 2.1.6 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | 4. Where fire-resistive construction is required, hoistways shall be enclosed in conformance with the requirements of the building code. Fire rating as per building code shall be maintained through EMT at top of hoistway, can see through conduit. Ref: 2.1.1.1.1 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.1.3.4 | Yes | No | 5. Floors shall be of concrete or metal construction with or without perforations for metal floors. A 1 inch round hole through machine room floor by machine shall be covered or patched. Ref: 2.1.3.4 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | 6. Safe and convenient access shall be provided to all pits, and shall conform to 2.2.4.1 through 2.2.4.4. This ladder is in no way a safe and convenient access to the pit. The reach for grabbing the ladder and exiting off the ladder is too much to be considered safe. Ref: 2.2.4 Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | 7. Pits shall be kept free of dirt and rubbish. Ref: 8.10.2.2.5(a) Re-inspect | 9/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | 1) Class “ABC” fire extinguishers shall be provided in elevator electrical machinery room and should be tagged to indicate monthly check and required annual maintenance.Tagged marked 08/2018. Ref: 8.6.1.6.5 | 11/1/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, governor tested, and buffers compressed before the inspection is completed. | 9/26/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate shall be posted in the machine room. | 10/11/2024 |