Inspection
Inspection Details
Equipment ID
13861
13861
Inspection Date
9/13/2023
9/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
61eb79fb-8c46-45f2-a526-e6f699305aac
61eb79fb-8c46-45f2-a526-e6f699305aac
Location
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 10/10/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 10/10/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test counterweight buffer at rated speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Need to replace missing capacity plate in car | 9/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, need to remove water and repair sump pump | 10/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace missing phase I and II fire service operating instructions signs. | 7/23/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When the elevator is on phase II fire service at the alternate landing, it will not revert back to phase I fire recall when the in car phase II fire service switch is turned to off. Needs repaired, Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Need to replace missing door gibb on 2nd floor Halldoor | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Need signs "In case of Fire, use Stairs" | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Doors do not stay open on Phase I fire service. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When the elevator is on phase II fire service at the alternate landing, it will not revert back to phase I fire recall when the in car phase II fire service switch is turned to off. Needs repaired, Re-inspection required |