Inspection
Inspection Details
Equipment ID
13860
13860
Inspection Date
9/13/2023
9/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
ccdc6537-6319-419e-9a3a-7fd1c6f08726
ccdc6537-6319-419e-9a3a-7fd1c6f08726
Location
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension means, diameter loss due to rouging exceeds proposed criteria. Needs replacement within 90 days. | 11/22/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 11/23/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter and are rouged, replace suspension ropes. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test counterweight buffer at rated speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car buffer, rated load & speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties, rated load & speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test machine brake with 125% rated load. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Replace illegible capacity plate in car | 9/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | No | Suspension ropes are below minimum diameter and are rouged, need to be replaced. Re-inspection required | 9/30/2024 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby is under minimum distance of 6". Hoist ropes need to be shortened. Re-inspection required | 9/30/2024 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Hoist ropes need to be shortened. Runby is below minimum of 6". Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Need to replace illegible capacity plate in car | 9/18/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Car comes down to the first floor egress, door close button does not work. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | No signs "In case of fire, use stairs" need to replace signs | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace illegible capacity plate in car |