Inspection
Inspection Details
Equipment ID
23179
23179
Inspection Date
10/12/2018
10/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
6725f225-393a-4167-9565-d0bb63b1d09c
6725f225-393a-4167-9565-d0bb63b1d09c
Location
EVO Apartments
9015 EAGER RD, SAINT LOUIS, MO
9015 EAGER RD, SAINT LOUIS, MO
Owner
MV One LLC
33 W MONROE ST, CHICAGO, IL 60603-5300
33 W MONROE ST, CHICAGO, IL 60603-5300
Billing
Attn: EVO Apartments
9015 EAGER RD, SAINT LOUIS, MO 63144-1180
9015 EAGER RD, SAINT LOUIS, MO 63144-1180
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Battery back system does not work. | 2/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Provide missing lobby warning placards on 2, 3 ,4 floors. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Hoistway door (all floors) missing fire stop on bottom of doors. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | Space where the MCP is stored, also contains disconnect needed for testing. This is an elevator space, only elevator related items allowed to be stored. | 6/19/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/27/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related equipment from the machine room | 8/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing IN CASE OF FIRE DO NOT USE THE ELEVATOR pictographs on floors 2, 3 & 4 | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | Emergency manual brake release shall work, needs repaired. Re-inspection required | 4/9/2025 |