Inspection
Inspection Details
Equipment ID
12355
12355
Inspection Date
10/3/2023
10/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
430
430
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
6ba8c01f-d1ec-474a-a349-af01e992a907
6ba8c01f-d1ec-474a-a349-af01e992a907
Location
Mary Grove Childrens Home
2705 Mullanphy Ln, Florissant, MO
Phone: (314) 837-1702
2705 Mullanphy Ln, Florissant, MO
Phone: (314) 837-1702
Owner
Attn: Mary Grove
Mary Grove Children's Home
2705 MULLANPHY LN, FLORISSANT, MO 63031
Phone: (000) 000-0000
Email: tquintanilla@mgstl.org
Mary Grove Children's Home
2705 MULLANPHY LN, FLORISSANT, MO 63031
Phone: (000) 000-0000
Email: tquintanilla@mgstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 10/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work on emergency power (pull 110v) | 1/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Car fan, on car top has no cover. Provide. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room ventilation unit not working, make so. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Sump pump in the pit is not plugged in. Determine if unit works, if not replace.if electrical issue then repair outlet. | 1/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Provide machine room door to be self closing. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 10/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work on emergency power | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car fan, on car top has no cover. Fan must have cover | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine room ventilation unit not working | 10/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump pump in the pit is not plugged in. Determine if unit works, if not replace. If electrical issue then repair outlet | 10/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room door to be self closing and self locking | 10/16/2025 |