Inspection
Inspection Details
Equipment ID
22520
22520
Inspection Date
10/2/2023
10/2/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23 / 24
23 / 24
External ID
66b421b0-b911-4621-9fea-fbe117a13f76
66b421b0-b911-4621-9fea-fbe117a13f76
Location
Arcade Building
816 Olive St, St. Louis, MO
Phone: (314) 607-7175
816 Olive St, St. Louis, MO
Phone: (314) 607-7175
Owner
Attn: St. Louis Leased Housing Association
St. Louis Leased Housing Association
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (763) 354-5500
St. Louis Leased Housing Association
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (763) 354-5500
Billing
Attn: Arcade Building
Dominium Management Services
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (763) 452-3155
Email: treiterman@dominiuminc.com
Dominium Management Services
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (763) 452-3155
Email: treiterman@dominiuminc.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair emergency light in car | 9/20/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | 17th floor broken lay and strands | 11/13/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | displayed certificate is not current | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Cartop light missing bulb and guard | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | Car riding lantern is missing cover, exposing electronics | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Excessive debris in pit, clean pit | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Shorten Gov Rope or adjust Tension device for sufficient travel | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | Replace missing Door Close button in COP | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | TESTING INCOMPLETE due to Maint Co. scheduling conflicts and issues. REMAINING: all weight tests, buffer tests, slide, | 9/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | There are no 5 year test tags on elevator equipment. Have elevator company performed 5 year test to tag equipment | 4/11/2023 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | Yes | No | Repair or replace damaged traveling cable | 5/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work | 5/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | No | No | Fire recall visual signal is missing from inside the elevator cab | 5/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | There are no 5 yr test tags on elevator equipment. Re-inspection required | 8/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair or replaced. Re-inspection required | 8/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 5/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean dirt, oil & debris from elevator car top | 4/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Rear car door restrictor does not work. Re-inspection required | 5/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Position indicator cover is missing, and shall be repaired Or replaced. | 12/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate shall be displayed inside of elevator machine room. | 12/2/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, need repaired. Re-inspection required | 2/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Position indicator cover is missing, and shall be repaired Or replaced. | 2/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, need repaired. Re-inspection required |