Inspection
Inspection Details
Equipment ID
15889
15889
Inspection Date
10/4/2023
10/4/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
610
610
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
78b7ab56-8913-4f95-8ba0-fab648c8bcd6
78b7ab56-8913-4f95-8ba0-fab648c8bcd6
Location
Emerson Electric - Building W
8100 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
8100 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
Owner
Attn: Jeff Chapin
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 623-6003
Alt Phone: (314) 568-4569
Email: Jeff.chapin@emerson.com
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 623-6003
Alt Phone: (314) 568-4569
Email: Jeff.chapin@emerson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working. Re-inspection required | 8/1/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 8/1/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs | 8/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in elevator machine room | 8/1/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 9/24/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 9/24/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs. (noted on previous report) | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Battery lowering device inoperable, repair or replace as needed. | 3/27/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Battery lowering device inoperable, needs repaired or replaced. Re-inspection required | 7/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Battery lowering device inoperable, repair or replace as needed. 8.6.4.19.7 | 3/3/2026 |