Inspection
Inspection Details
Equipment ID
12065
12065
Inspection Date
10/2/2023
10/2/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
64e81d89-72ef-4221-a20e-de94affcf2f1
64e81d89-72ef-4221-a20e-de94affcf2f1
Location
Curlee Building
611 N 10th St, St. Louis, MO
Phone: (314) 531-3535
Alt Phone: (314) 565-0939
611 N 10th St, St. Louis, MO
Phone: (314) 531-3535
Alt Phone: (314) 565-0939
Owner
Attn: Sol Zelcer
770 Curlee, LLC
611 N 10 St, St. Louis, MO 63101
Phone: (000) 000-0000
Email: solzelcer@gmail.com
770 Curlee, LLC
611 N 10 St, St. Louis, MO 63101
Phone: (000) 000-0000
Email: solzelcer@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The fire extinguisher in the machine room shall be serviced (Expired 2016). | 3/18/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing. | 3/18/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Pipes conveying liquid are not permitted in the hoistway. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair the pit lighting. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)8 | No | No | Egress shall not be blocked by door at 7th floor. | 3/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | In car emergency stop switch shall be overridden on Phase 1 fire service. | 2/10/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key. | 3/18/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 8/25/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | The counterweight guard shall extend from a point not more than 12" above the pit floor. | 3/18/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The in car lighting shall be guarded. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Pipes conveying liquids, gases, or vapors shall not be located in the hoistway. The copper pipe in the overhead shall be removed. | 3/18/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit lighting shall be operational. | 3/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 fire service shall be operational. (Violation to be corrected no later than April 17th, 2020. | 8/25/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed that shall be replaced. | 3/18/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The counterweight is compressing the buffer with the car level at the top landing. Counterweight runby shall be provided. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclose shall be of a solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | 3/18/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 8/25/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. | 8/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 8/25/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 1 foot of standing water in it. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. | 3/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 3/9/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Needs annual test completed after cleaning and removing rust from pistons. Re-inspection required | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | Yes | Yes | Repair or replace defective car and counterweight buffers. Red-tagged, Re-inspection required |