Inspection
Inspection Details
Equipment ID
15848
15848
Inspection Date
9/28/2023
9/28/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
11752c28-8fbd-4afc-b9fd-3b278b01e559
11752c28-8fbd-4afc-b9fd-3b278b01e559
Location
King Bee Condos
1709 Washington Ave, St. Louis, MO
Phone: (314) 504-3796
1709 Washington Ave, St. Louis, MO
Phone: (314) 504-3796
Owner
Attn: Julie Ker
King Bee Lofts c/o Smith Management Group
1630 Des Peres Rd, Ste 210, St. Louis, MO 63131
Phone: (314) 394-4200
Email: jker@smithmgmt.com
King Bee Lofts c/o Smith Management Group
1630 Des Peres Rd, Ste 210, St. Louis, MO 63131
Phone: (314) 394-4200
Email: jker@smithmgmt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection is required. | 8/1/2018 |
| conversion | conversion | n/a | No | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 11/13/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/1/2018 |
| conversion | conversion | n/a | No | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the ?off? position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 11/13/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elvator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Re-inspection is required. | 9/14/2018 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Re-inspection is required. | 9/14/2018 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Hoist ropes are rouged and approaching minimum diameter. Replace within 90 days. | 7/29/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall work. | 7/29/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/14/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/28/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergrncy alarm bell and emergency light shall work when on auxiliary power |