Inspection
Inspection Details
Equipment ID
5879
5879
Inspection Date
9/15/2023
9/15/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Bobby Strader
Bobby Strader
Relief Valve Pressure
NA
NA
Slide
TBD
TBD
Governor Rope Pull
30/680
30/680
Door Closing Force
TBD
TBD
External ID
ddec16b0-e761-4ed6-b1d3-8c2b3fa2096f
ddec16b0-e761-4ed6-b1d3-8c2b3fa2096f
Location
Dulle Tower
10 Jackson St, Jefferson City, MO
Phone: (573) 635-6163
10 Jackson St, Jefferson City, MO
Phone: (573) 635-6163
Owner
Attn: Jefferson City Housing Authority
Jefferson City Housing Authority
1040 Myrtle Ave, Jefferson City, MO 65109
Phone: (573) 635-6163
Jefferson City Housing Authority
1040 Myrtle Ave, Jefferson City, MO 65109
Phone: (573) 635-6163
Billing
Attn: Jefferson City Housing Authority
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163 Ext: 203
Email: Rachel@jchamo.org
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163 Ext: 203
Email: Rachel@jchamo.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | Machine room upper handrail is loose. Repair or replace. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine room shall have GFCI outlet. It is currently a standard outlet. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | 4x4 electrical box in machine room needs to have wiring inside box and cover installed. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Machinery, controllers, governors & disconnects shall be numbered conspicuously. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | NEC 110.26 - Disconnects do not meet 30" rule i.e. not co-planer. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | 2.24.8 - Machine brake holding adjustment shall be properly sealed to prevent unauthorized adjustment. | 9/15/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Building fire alarm initiating devices/panel not currently wired to elevator controller. Must be tested for proper FAID recall operation prior to public use. | 9/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete. Elevator shut down during testing. Category 1 & 5 testing items shall be witnessed. | 9/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Testing is incomplete. Unable to complete tests due to shutdown during test. Items remaining: 125% unintended movement down, 100% safety set, slide, fire service 1 & 2, door force. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Machinery, controllers, governors & disconnects shall be numbered conspicuously. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.27 - Rope fastenings | 2.20.9 | Yes | No | Suspension rope tail ends shall be properly seized/banded. | 9/19/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Cartop wireway and 4x4 box covers to be installed. | 9/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust upthrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 9/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone breaking up and full of static. Contact can't tell location. | 11/8/2025 |