Inspection
Inspection Details
Equipment ID
16909
16909
Inspection Date
9/27/2023
9/27/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
444b9fd5-636f-4c08-a2bb-757af68e62cc
444b9fd5-636f-4c08-a2bb-757af68e62cc
Location
The Garden @ Renaissance
3117 Thomas St, St. Louis, MO
Phone: (314) 652-8900
3117 Thomas St, St. Louis, MO
Phone: (314) 652-8900
Owner
Attn: McCormack, Baron Ragan
Senior Livings & Gardens @ Renaissance
3217 Martin Luther King Dr, St. Louis, MO 63101
Phone: (314) 652-8900
Email: renaissancegardens@mccormackbaron.com
Senior Livings & Gardens @ Renaissance
3217 Martin Luther King Dr, St. Louis, MO 63101
Phone: (314) 652-8900
Email: renaissancegardens@mccormackbaron.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace damaged fire service signage in car. | 4/18/2019 | ||
conversion | conversion | n/a | Pit light shall work. | 4/18/2019 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The auxiliary battery lowering shall be operational. | 11/16/2022 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed) | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/27/2023 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 9/27/2023 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State operating certificate in machine room. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide current tested fire extinguisher in machine room. | |||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lighting shall properly operate. | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up-to-date operating certificate required in the machine room. | |||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lights shall work. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | ||
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. |