Inspection
Inspection Details
Equipment ID
2826
2826
Inspection Date
10/2/2023
10/2/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
4de531c5-7b8d-4427-a765-e5743875ba28
4de531c5-7b8d-4427-a765-e5743875ba28
Location
Sioux Power Plant
8501 N State Rte 94, West Alton, MO
Phone: (800) 552-7583
8501 N State Rte 94, West Alton, MO
Phone: (800) 552-7583
Owner
Attn: Megan Ratterree
Ameren Missouri- Sioux Plant
8501 N State Rte 94, West Alton, MO 63386
Phone: (314) 206-1930
Email: MRatterree@ameren.com
Ameren Missouri- Sioux Plant
8501 N State Rte 94, West Alton, MO 63386
Phone: (314) 206-1930
Email: MRatterree@ameren.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Missing code data plate | 8/3/2018 |
| conversion | conversion | n/a | No | No | Repair broken control room door (will not close) | 8/3/2018 |
| conversion | conversion | n/a | No | No | Lights inside cab cahll be guarded. | 8/3/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair Door Restrictor (Reinspect) | 10/9/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room of non-elevator equipment. | 12/1/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher needs to be serviced. | 12/1/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | H.1 - The drop ceiling in the machine room is degrading due to water seepage and shall be repaired. | 9/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 5/4/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power | 8/26/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine Space shall have at least one(1) GFCI outlet. Currently available outlet | 8/26/2026 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 2.29.1 | Yes | No | Machinery, controllers, governors, disconnects shall be numbered conspicuously. | 8/26/2026 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.18.3 | Yes | No | Governor - Speed governors shall have their means of speed adjustment sealed after test. | 8/26/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | Yes | No | Unintended Motion shall be a maximum of 48" | 8/26/2026 |
| A17.1-2016 : Elevators | 3.27 - Crosshead data plate | 8.7.2.17.3 Decrease in Rated Speed | Yes | No | Suspension and Governor ropes shall have proper data tag(s) See also 2.18.5.3 & Rule211.2b | 8/26/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | Yes | No | Fire Service Phase 1 switch at level 446 not working | 8/26/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) | Yes | No | Fire Alarm Initiating Devices at 446 shall recall to 465(main). FAID at 465 shall recall to 446(ALT). FAID at 430 shall have solid hat, not flashing. | 8/26/2026 |