Inspection
Inspection Details
Equipment ID
19008
19008
Inspection Date
9/25/2023
9/25/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
600
600
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
00c80ca5-ad15-4e55-8f04-f98a81fb40cc
00c80ca5-ad15-4e55-8f04-f98a81fb40cc
Location
St. Louis Gateway Transportation Center
430 S 15th St, St. Louis, MO
Phone: (314) 622-4635
430 S 15th St, St. Louis, MO
Phone: (314) 622-4635
Owner
Attn: Rick Ernst
City of St. Louis
1200 Market St, Rm 301, St. Louis, MO 63103
Phone: (000) 000-0000
Email: ernstr@stlouis-mo.gov
City of St. Louis
1200 Market St, Rm 301, St. Louis, MO 63103
Phone: (000) 000-0000
Email: ernstr@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Machine room shall not be used for storage of non-elevator related materials. | 12/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 11/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation year, a category 5 test is due on or before the next annual inspection. | 9/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 11/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Where auxiliary lowering operation is provided, it shall conform to 3.26.10 through 3.26.10.3. Note: Does not pick retiring cam, therefore car stops 12"-18" above the floor. | 7/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Record monthly fire service testing. Log is blank from 2/2022 to 7/2023. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Where auxiliary lowering operation is provided, it shall conform to 3.26.10 through 3.26.10.3. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Where auxiliary lowering operation is provided, it shall conform to 3.26.10.1 through 3.26.10.3. (FINAL NOTICE) | 7/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | Fire service phase 1 switch - works intermittently. | 7/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing shall be documented monthly. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | Cartop light does not work. | 11/24/2025 |