Inspection
Inspection Details
Equipment ID
11327
11327
Inspection Date
10/10/2023
10/10/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Suedkamp
Robert Suedkamp
Relief Valve Pressure
510
510
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
22 / 24
22 / 24
External ID
a83fa6c9-6ac2-40c0-8d99-49b9bb61d0b8
a83fa6c9-6ac2-40c0-8d99-49b9bb61d0b8
Location
Steinberg Hall/Steinberg-Givens Link
6253 Forsyth Blvd, St. Louis, MO
Phone: (314) 935-6038
6253 Forsyth Blvd, St. Louis, MO
Phone: (314) 935-6038
Owner
Attn: Drew Thompson
Washington University in St. Louis MO/Facilities Planning and Management
One Brooking Dr, Campus Box 1036, St. Louis, MO 63130
Phone: (314) 348-0098
Alt Phone: (314) 935-6038 Ext: 314-795-0965
Email: drew.thompson@wustl.edu
Washington University in St. Louis MO/Facilities Planning and Management
One Brooking Dr, Campus Box 1036, St. Louis, MO 63130
Phone: (314) 348-0098
Alt Phone: (314) 935-6038 Ext: 314-795-0965
Email: drew.thompson@wustl.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | Channel drain in pit, over sump hole | 2/13/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | x | The door close button shall be operational. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | x | x | Phase 2 fire service shall be operational. (Could not test because door close button did not work). | 9/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.39 - Low Oil Protection | 3.26.9 Low Oil Protection (Re-Inspection) | x | Low oil protection shall be operational. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(c) | x | Machine room lights bulbs shall be guarded. | 9/10/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | x | Debris shall be removed from the car top. The car top shall be cleaned. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | x | The machine room shall be kept clean. Remove the debris from the machine room. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Wireway covers and end caps shall be installed. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | x | Heat detector in machine room shall remove power from the elevator when activated. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Heat detector in hoistway shall remove power from the elevator when activated. | 9/10/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Smoke detector at 2nd floor shall be operational and recall to the main landing. | 9/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Smoke detector at 1st floor rear entry shall recall to the main landing. | 9/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Smoke detectors in machinery spaces shall recall to the main landing. | 9/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Fire panel module in overhead shall be installed in the correct size box. | 9/10/2019 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Need maintenance control program on site posted on controller | 1/17/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the elevator machine room | 1/17/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV is due for 5 year test in 2024 | 1/17/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the elevator machine room | 1/17/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room |