Inspection
Inspection Details
Equipment ID
13662
13662
Inspection Date
10/3/2023
10/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
77ea28b8-6961-4889-912a-25962083d62c
77ea28b8-6961-4889-912a-25962083d62c
Location
Kiener East Garage
500 Pine St, St. Louis, MO
Phone: (314) 241-4262
500 Pine St, St. Louis, MO
Phone: (314) 241-4262
Owner
Attn: Inter Park Holdings LLC
Inter Park Holdings LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Inter Park Holdings LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need phase 2 fire signage in car. | 1/15/2021 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light and bell shall work. | 10/1/2018 |
| conversion | conversion | n/a | No | No | Position indicator in car shall work | 1/15/2021 |
| conversion | conversion | conversion - reinspect | Yes | No | Return to phase 1 fire service did not work when turning phase 2 switch to off. | 10/1/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Door close operation shall require constant pressure on phase 2 fire service. | 10/1/2018 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | A category 5 inspection is required. | 10/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 1 and Phase 2 key switches shall be keyed the same. | 10/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 2 instructions in the car. | 10/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell shall work. | 10/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency lights shall work. | 1/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The lighting in the stairwell that leads to the machine room shall be operational. | 12/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Car failed unintended motion test with 125% load, did not stop within allowed distance. Elevator Red Tagged. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Mainline disconnect broke during testing and needs repair. Elevator Red Tagged. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The remainder of the annual and category 5 test needs to be completed. Note: Hoistway, hall door interlocks, car gate switch and restrictor, emergency light, alarm, 2 way-communication, and fire service have been inspected. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Unit is still under red tag condition. Unintended motion with 125% load and counterweight buffer testing must be performed to complete category 5 testing and remove red tag. | 12/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |