Inspection
Inspection Details
Equipment ID
4755
4755
Inspection Date
10/6/2023
10/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
3fef80d1-06bd-413c-acce-ff0a9cbd9ef9
3fef80d1-06bd-413c-acce-ff0a9cbd9ef9
Location
MO Baptist Medical Center-Bldg C
3009 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5346
3009 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5346
Owner
Attn: BJC C/O Cushman And Wakefield Eager Rd
BJC C/O Cushman And Wakefield Eager Rd
3009 N Ballas Rd, St. Louis, MO 63131
Phone: (000) 000-0000
BJC C/O Cushman And Wakefield Eager Rd
3009 N Ballas Rd, St. Louis, MO 63131
Phone: (000) 000-0000
Billing
Attn: BJC C/O Cushman And Wakefield Eager Rd
BJC C/O Cushman And Wakefield Eager Rd
8300 Eager Rd, Ste 600, St. Louis, MO 63144
Phone: (314) 996-5346
Email: bjcinvoices@cushwake.com
BJC C/O Cushman And Wakefield Eager Rd
8300 Eager Rd, Ste 600, St. Louis, MO 63144
Phone: (314) 996-5346
Email: bjcinvoices@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | Bottom stop switch cover buzzer not working | 1/10/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | Upper left handrail inlet guard needs to be replaced | 1/10/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | lower left handrail inlet guard needs to be replaced | 1/10/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | Bottom left lower balustrade gap exceeds maximum allowable | 1/10/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | Demarcation lights not working | 1/10/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | x | A17.2 - 7.17 - The step indexing loaded gap shall not be greater than 4.8mm on each side. | 9/10/2021 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | x | 8.6.8.3 - The step/skirt performance index shall not exceed .4. | 9/10/2021 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | x | Top & bottom demarcation lamps shall be operational. | 9/10/2021 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | x | Bottom demarcation lamps shall be operational. | 9/10/2021 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.6.2(i) Step Demarcation | x | The top and bottom demarcation lights shall be operational. | 10/6/2023 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | x | The loaded step gap shall not exceed 4.8mm on either side. | 10/6/2023 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | x | The escalator step/skirt performance index shall not exceed .4. | 10/6/2023 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.11.4.1(e) Lighting (demarcation and step lighting) | x | 8.6.11.6.2(i) Step Demarcation - The top and bottom demarcation lights shall be operational. (2nd Notice) | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | x | The loaded step gap shall not exceed 4.8 mm on either side. (2nd Notice) | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | x | Performance index shall not exceed 0.4. (2nd Notice) | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | x | Handrails will be free of major cracks and pinch points. Replace left handrail. | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | Replace damaged lower key up/down switch. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided. MCP shall be present and updated. |