Inspection
Inspection Details
Equipment ID
8882
8882
Inspection Date
8/22/2023
8/22/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
480
480
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
1623ae7c-1992-43e6-84fa-ea9a55076b64
1623ae7c-1992-43e6-84fa-ea9a55076b64
Location
William Chrisman High School
1223 N Noland Rd, Independence, MO
Phone: (816) 521-2720
1223 N Noland Rd, Independence, MO
Phone: (816) 521-2720
Owner
Attn: Sarah Barker
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: SARAH_BARKER@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: SARAH_BARKER@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Need to perform and post monthly fire service test log in the elevator machine room | 11/25/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | do not store non-elevator related material in the machine room | 11/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | provide working phone line to the elevator controller, the phone line that is there is dead. | 7/27/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | n/a | No | No | Provide a ABC fire extinguisher convenient to the access door | 2/23/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | backup battery failed to operate | 2/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The firefighters service test log is not being filled out monthly. | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | could not find an oil record log in the machine room | 1/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | label the controller, tank, disconnect, car top, and pit Elevator #2 | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | the next overspeed valve test will be due in 2022 | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | could not find Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | did not find monthly fire service test log in the machine room | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Only one emergency light bulb worked, replace burnt out emergency light bulb | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Door restrictor missing parts, repair door restrictor so it works |