Inspection
Inspection Details
Equipment ID
20709
20709
Inspection Date
10/10/2018
10/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Edward Barfield
Edward Barfield
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
6b5c43e8-3d93-4359-8021-ff3333c3d097
6b5c43e8-3d93-4359-8021-ff3333c3d097
Location
Peabody Opera House
1400 MARKET ST, SAINT LOUIS, MO
1400 MARKET ST, SAINT LOUIS, MO
Owner
Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103-2700
1401 CLARK AVE, SAINT LOUIS, MO 63103-2700
Billing
Attn: Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103-2700
1401 CLARK AVE, SAINT LOUIS, MO 63103-2700
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 8.11.4.2.9 | Yes | No | Replace broken step treads. | 10/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 8.6.8.6 | Yes | No | There are three treads that have broken teeth. Reinspect within 90 days. | 12/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.14 | No | No | Upper and lower machine spaces are dirty and need cleaned. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.12 - Steps, step chains, and trusses | 8.11.4.2.12 | No | No | Entire truss needs to be cleaned out. | 9/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 6.1.6.7 | No | No | Lower demarcation lights don't work. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.10 - Operating and safety devices | 6.1.6.3.1 Emergency Stop Buttons (Re-Inspection) | Yes | No | Upper level emergency stop switch cover does not have a buzzer when opened. | 12/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.6 - Caution Signs | 6.1.6.9 | No | No | There needs to be caution signs posted on top and bottom landings of the escalator. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 8.6.8.4 Combplates | Yes | No | A center combplate on upper end has a broken tooth, replace same | 9/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Down combplate impact center and left settings exceed maximum allowable by code, adjust, repair & re-test. Re-inspection required | 9/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform required brake torque testing. Re-inspection required | 9/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform missing step testing. Re-inspection required | 9/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 8.6.8.4 Combplates | Yes | No | Upper end has comb plate, broken tooth. | 12/1/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide brake torque test. | 12/1/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide missing step test. | 12/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.10 - Operating and safety devices | 6.1.6.3.1 Emergency Stop Buttons (Re-Inspection) | Yes | No | Transparent cover missing from lower landing emergency stop switch. Install transparent cover. Re-inspection required | 2/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Lower landing demarcation lights do not work, need repaired. Re-inspection required | 2/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Perform step indexing test. Re-inspection required | 2/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Top of escalator demarcation light not working. Re-inspection required | 4/10/2026 |