Inspection
Inspection Details
Equipment ID
12088
12088
Inspection Date
10/23/2023
10/23/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Kyle Ritchhart
Kyle Ritchhart
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
7882c36c-3ccb-43c9-bdbc-cca0727d4ec7
7882c36c-3ccb-43c9-bdbc-cca0727d4ec7
Location
LaQuinta Inn
2214 Taney St, N Kansas City, MO
Phone: (816) 221-1200
2214 Taney St, N Kansas City, MO
Phone: (816) 221-1200
Owner
Attn: Sue McNish
North Kansas City Hospitality DBA LaQuinta Inn
2214 Taney St, N Kansas City, MO 64114
Phone: (816) 221-1200
Email: sue@premierhotelskc.com
North Kansas City Hospitality DBA LaQuinta Inn
2214 Taney St, N Kansas City, MO 64114
Phone: (816) 221-1200
Email: sue@premierhotelskc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove sprinkler head from ceiling above controller, no heat detector or shunt trip present. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide an MCP in machine room to log maintenance, repairs, and inspections. | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide a 5 gallon pit jug in pit to collect leakage from jack packing. | 8/1/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | Main line disconnect has broken component inside, replace disconnect switch in machine room. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Handrail missing in car. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Handrail loose in car. | 8/1/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Stop switch on car operating panel worn, and not legible. Replace | 8/23/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Position indicator on COP not displaying floor numbers. | 8/1/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machine room door not self locking provide self looking door handle | 8/25/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach. room door lock defeatable | 10/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 10/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working not answered | 10/23/2023 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.14.2 Hydraulic Cylinders and Pressure Piping | Yes | Yes | leak down test failed dropped 2 inches in 15 mins futher testing required no shutoff valve | 10/23/2023 |