Inspection
Inspection Details
Equipment ID
2808
2808
Inspection Date
10/25/2023
10/25/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
8e99babe-319d-441c-acaf-f53508575446
8e99babe-319d-441c-acaf-f53508575446
Location
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO
Phone: (636) 947-5000
Email: michelle.deckard@ssmhealth.com
300 1st Capitol Dr, St. Charles, MO
Phone: (636) 947-5000
Email: michelle.deckard@ssmhealth.com
Owner
Attn: SSM Health- ESEP Department
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
Billing
Attn: Andy Gratton
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5000
Email: Andrew.gratton@ssmhealth.com
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5000
Email: Andrew.gratton@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Phase I fire service key switch bezel at main landing is unreadable, replace same | 10/14/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Overspeed governor rope is damaged, replace same. Re-check pull out / pull thru when rope is replaced. Red-tagged. Re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties were damaged during testing, repair or replace and re-inspect with full load, at contract speed. Red-tagged, Re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)6 | Yes | Yes | Overspeed governor speed switch is set too close to jaw tripping speed. Adjust and re-inspect. Red-tagged, re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work. Re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman's emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required | 10/14/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman's emergency service phase I instruction adjacent to the keyed switch at the primary egress floor, as required | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Phase I fire service key switch bezel at main landing is unreadable, needs to be replaced | 10/14/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work. Re-inspection required | 4/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Counterweight runby is 1 inch. Minimum runby is 6 inches. Hoist ropes need to be shortened to achieve at least 6 inches runby, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. |