Inspection
Inspection Details
Equipment ID
15009
15009
Inspection Date
10/16/2023
10/16/2023
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
William Bracht
William Bracht
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
70/680
70/680
Door Closing Force
NA
NA
External ID
0638230d-6305-4dca-938e-63a70a4bde82
0638230d-6305-4dca-938e-63a70a4bde82
Location
Grace Lofts
1324 Washington Ave, St. Louis, MO
Phone: (314) 588-1170
1324 Washington Ave, St. Louis, MO
Phone: (314) 588-1170
Owner
Attn: Park Side Lofts LLC c/o MBD Management LLC
Park Side Lofts LLC c/o MBD Management LLC
1220 St. Charles st, St. Louis, MO 63103
Phone: (314) 526-9769
Email: ranchoffice@protonmail.com
Park Side Lofts LLC c/o MBD Management LLC
1220 St. Charles st, St. Louis, MO 63103
Phone: (314) 526-9769
Email: ranchoffice@protonmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | The car door restrictor shall work. | 1/10/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency lighting shall work. | 1/10/2020 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Independent service does not keep the doors open. | 1/10/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Phase 2 fire service does not work. Phase 2 fire service shall be repaired and retested. | 1/10/2020 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | Yes | No | Repair the broken conduit on the car buffer switch. | 1/10/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | No | No | The car ceiling is about to fall down. Take corrective action to properly repair the car ceiling. | 9/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car & hoistway doors need to be adjusted for proper alignment and operation. | 8/12/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light inside car does not work. | 10/16/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 10/16/2023 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Hoistway ropes are rouged and nearing the minimal allowable diameter and meet the criteria for replacement. | 10/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | The roller guide on the front left side of the car top while facing the hall doors needs to be replaced. | 4/2/2025 |