Inspection
Inspection Details
Equipment ID
863
863
Inspection Date
10/25/2023
10/25/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard Hawkins
Richard Hawkins
Relief Valve Pressure
420
420
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15/15
15/15
External ID
0f44e910-c22f-4826-9cd7-a07156499a09
0f44e910-c22f-4826-9cd7-a07156499a09
Location
Memorial Baptist Church
4001 Fair Ave, St. Louis, MO
Phone: (314) 652-0370
4001 Fair Ave, St. Louis, MO
Phone: (314) 652-0370
Owner
Attn: Memorial Baptist Church
Memorial Baptist Church
4001 Fair Ave, St. Louis, MO 63115
Phone: (314) 518-4941
Email: memorialstl@memorialmbcstl.com
Memorial Baptist Church
4001 Fair Ave, St. Louis, MO 63115
Phone: (314) 518-4941
Email: memorialstl@memorialmbcstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair inoperative emergency phone. | 9/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair inoperative alarm. | 9/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair emergency light. | 9/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide updated fire extinguisher. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work properly. Signal not present at elevator control panel. | 3/2/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work (phone line has no power) | 10/25/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit full of 5 gallon buckets and hydraulic fluid. Clean pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor does not work. Repair | 10/25/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | 8/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. Oil and buckets. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear door restrictor (rear) not working properly, repair/replace as needed. | 8/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase I instructions near the f/f switch in the lobby. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Post current State Elevator Certificate | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | Yes | No | Remove fluids from the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Dorr restrictor (rear) out of adjustment, repair as needed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. |