Inspection
Inspection Details
Equipment ID
1432
1432
Inspection Date
10/17/2023
10/17/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
400
400
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
25
25
External ID
9167a954-4b0b-47ce-a96a-f19a47347511
9167a954-4b0b-47ce-a96a-f19a47347511
Location
Macy's- South County
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-0110
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-0110
Owner
Attn: TSG PROPERTIES
TSG PROPERTIES
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (314) 471-4975
TSG PROPERTIES
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (314) 471-4975
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace missing cover on starter panel in machine room | 12/6/2019 |
| conversion | conversion | n/a | No | No | Post current state certificate in machine room | 12/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top emergency exit has to secured shut, openable without use of any tools | 12/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program and post on controller | 10/2/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and record on log in machine room | 10/2/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current Mo State certificate in machine room | 10/2/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repalce broken tile strip at sill inside the cab tripping hazard | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair leaking pump unit | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Overspeed valve not sealed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove excessive oil form machine drip pan. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post certificate in machine room. |